Does Ontario's Code require Type X between an attached garage and the house?

Question

Does Ontario's Code require Type X between an attached garage and the house?

Answer from Drywall Pro IQ

No. Ontario's Building Code does not require Type X drywall, 5/8-inch board, or any fire rating between an attached garage and the house it serves.

The rule that applies is clause 9.10.9.18 of Ontario's Building Code. Where a storage garage serves only the dwelling unit it is attached to or built into, the Code treats the garage as part of that dwelling unit and does not require a fire separation between them. What the Code does require is an air barrier system between the garage and the rest of the house, installed to conform to Subsection 9.25.3, that provides a continuous and effective barrier to gas and exhaust fumes. Every joint in a panel-type air barrier must be sealed, and penetrations such as electrical wiring, electrical boxes, piping and ductwork must also be sealed.

The door between the garage and the house has its own requirements under clause 9.10.13.15: it must be tight-fitting, weather-stripped, and fitted with a self-closing device, and the doorway must not open into a room intended for sleeping. Ask the contractor what they propose for the self-closing device and how it meets 9.10.13.15.(1).

These are minimums for new work, and you should ask the City of Ottawa's Building Code Services how they apply to your specific renovation.

What the Code focuses on for this wall and ceiling is continuity and sealing, not a particular board type or thickness. Taped and sealed drywall can form that gas barrier, because the taped joints and sealed penetrations are what the Code is asking for. If there are holes in the garage-side wall or ceiling, those should be patched and all penetrations sealed so the barrier is continuous. The Code's explanatory note adds that masonry garage walls should be sealed, plastered, or covered with gypsum wallboard on the garage side with all joints sealed, though that note is explanatory rather than a requirement.

The interior finish side is also worth noting: clause 9.35.4.1.(1) says interior finish need not be applied to garage and carport walls, so the garage side of the wall has no mandatory board finish under that section.

If the house was built before 1990, Health Canada advises testing before anyone cuts, sands, or scrapes existing material; a positive result means abatement work, and ottawaabatement.com covers that.

Have the contractor put in writing exactly which surfaces they will seal, how penetrations will be treated, and what they propose for the door's self-closing device.

Ottawa Drywallers

Want this done at your place?

Tell us what needs patching, replacing or boarding and we'll send it to local Ottawa drywall contractors, who reply by email. We send it out to local contractors for you. Free, no pressure.

Fields marked are required.

We won't call you. There's no phone box above because we don't ask for one — your estimate comes by email, on your time.

Request received We’ve sent your details to local Ottawa drywall contractors. Interested contractors reply by email. A confirmation is on its way to your inbox.

Drywall Pro IQ -- Built from the Ontario Building Code, Ontario regulations and City of Ottawa sources and real construction experience. Answers are for informational purposes only and are not a professional assessment.

Ready to Get Quotes?

Find local drywall contractors in Ottawa. Free matching, no obligation.

Find a Drywall Contractor